樓主  發表于: 2016-12-18 09:49
除塵系統315-2 拖2個ET200m站點,意外停機,后來重啟CPU 好了,不知道原因。故障時候SF BF STOP 燈常亮。請各位老師不吝賜教,謝謝!

Diagnostic buffer of module CPU 315-2 DP

Order No./ Description         Component                      Version                      
6ES7 315-2AH14-0AB0            Hardware                       6                            
- - -                          Firmware                       V 3.3.11                      
Boot Loader                    Firmware expansion             A 37.12.12                  

Rack:                          0
Slot:                          2


Serial number: S C-F6DW50132015


Event 1 of 10:  Event ID 16# 4302
Mode transition from STARTUP to RUN
Startup information:
- Time for time stamp at the last backed up power on
- Single processor operation
Current/last startup type:
- Warm restart triggered by switch setting; last power on backed up
Permissibility of certain startup types:
- Manual warm restart permitted
- Automatic warm restart permitted
Last valid operation or setting of automatic startup type at power on:
- Warm restart triggered by switch setting; last power on backed up
Previous operating mode: STARTUP (warm restart)
Requested operating mode: RUN
Incoming event
08:30:11.743 AM  03/10/1995
(Coding: 16# 4302  FF68  C700  0000  0813  7713)


Event 2 of 10:  Event ID 16# 1381
Request for manual warm restart
Startup information:
- Startup without modified system configuration
- No difference between setpoint and actual configuration
- Time for time stamp at the last backed up power on
- Single processor operation
Current/last startup type:
- Warm restart triggered by switch setting; last power on backed up
Permissibility of certain startup types:
- Manual warm restart permitted
- Automatic warm restart permitted
Last valid operation or setting of automatic startup type at power on:
- Warm restart triggered by switch setting; last power on backed up
Requested OB: Startup OB (OB100)
OB not found, or disabled, or cannot be started in the in the current operating mode
Incoming event
08:30:11.742 AM  03/10/1995
(Coding: 16# 1381  FE64  C772  0000  0813  7713)


Event 3 of 10:  Event ID 16# 4301
Mode transition from STOP to STARTUP
Startup information:
- Time for time stamp at the last backed up power on
- Single processor operation
Current/last startup type:
- Warm restart triggered by switch setting; last power on backed up
Permissibility of certain startup types:
- Manual warm restart permitted
- Automatic warm restart permitted
Last valid operation or setting of the automatic startup type at power on:
- Warm restart triggered by switch setting; last power on backed up
Previous operating mode: STOP (internal)
Requested operating mode: STARTUP (warm restart)
Incoming event
08:30:11.653 AM  03/10/1995
(Coding: 16# 4301  FF46  C772  0000  0813  7713)


Event 4 of 10:  Event ID 16# 38C4
Distributed I/Os: station return
Address of the affected DP slave: station number:    7
DP master system ID:      1
Log. base address of the DP slave: Input address:  2044
Log. base address of the DP master:   2047
Requested OB: Rack failure OB (OB86)
OB not found, or disabled, or cannot be started in the current operating mode
External error, Outgoing event
08:19:18.320 AM  03/10/1995
(Coding: 16# 38C4  FE56  C054  07FF  07FC  0107)


Event 5 of 10:  Event ID 16# 38C4
Distributed I/Os: station return
Address of the affected DP slave: station number:    6
DP master system ID:      1
Log. base address of the DP slave: Input address:  2046
Log. base address of the DP master:   2047
Requested OB: Rack failure OB (OB86)
OB not found, or disabled, or cannot be started in the current operating mode
External error, Outgoing event
08:19:08.663 AM  03/10/1995
(Coding: 16# 38C4  FE56  C054  07FF  07FE  0106)


Event 6 of 10:  Event ID 16# 5371
Distributed I/Os: End of the synchronization with a DP master/IO controller  on slot   2
Number of distributed stations:   2
Incoming event
08:19:07.904 AM  03/10/1995
(Coding: 16# 5371  FF02  C150  0002  0000  0000)


Event 7 of 10:  Event ID 16# 4358
All modules are ready for operation
Operating mode: STOP (internal)
Incoming event
08:19:05.462 AM  03/10/1995
(Coding: 16# 4358  FF44  0000  0000  0000  0000)


Event 8 of 10:  Event ID 16# 4357
Module monitoring time started
Operating mode: STOP (internal)
Incoming event
08:19:04.184 AM  03/10/1995
(Coding: 16# 4357  FF44  0000  0000  0000  0000)


Event 9 of 10:  Event ID 16# 430E
Memory reset executed
Previous operating mode: STOP (memory reset)
Requested operating mode: STOP (own initialization)
Incoming event
08:19:00.952 AM  03/10/1995
(Coding: 16# 430E  FF23  0000  0000  0000  0000)


Event 10 of 10:  Event ID 16# 4546
STOP caused by CPU memory management
Previous operating mode: STOP (own initialization)
Requested operating mode: STOP (memory reset)
Internal error, Incoming event
08:18:58.337 AM  03/10/1995
(Coding: 16# 4546  FF32  C0C0  8FFE  0000  0000)

volcanol
級別: 探索解密
精華主題: 0
發帖數量: 17 個
工控威望: 107 點
下載積分: 835 分
在線時間: 11(小時)
注冊時間: 2010-01-04
最后登錄: 2024-07-17
查看volcanol的 主題 / 回貼
1樓  發表于: 2016-12-24 13:54
DP從站丟失引起機架錯誤,導致停機。

如果要避免停機增加OB86組織塊,并下載到PLC中,可以避免停機。

但是不能消除DP從站丟失的故障,檢查DP通訊。
guang886622
級別: 略有小成
精華主題: 0
發帖數量: 191 個
工控威望: 304 點
下載積分: 17781 分
在線時間: 110(小時)
注冊時間: 2013-02-03
最后登錄: 2024-03-14
查看guang886622的 主題 / 回貼
2樓  發表于: 2016-12-24 17:48
是不是DP通訊頭有問題,之前我這里也出現故障,更換DP通訊頭好了

主站蜘蛛池模板: 国产精品视频一区二区三区经| 白鹿扒开内裤露出尿孔| 女攻双性| 海角社区在线登录| 午夜综合| 爱情岛论坛亚洲一号路线| 日本色播| 爱草视频| 日本性生活免费看| 精品一卡2卡3卡4卡5卡亚洲| 91美女在线| 窝窝色资源站| 精品国产一级毛片大全| 亚洲精美视频| bedfriend泰剧全集免费观看| 日本漫画工囗全彩番在线| 99精品国产成人一区二区在线| 亚洲天堂网站在线| 欧美一区高清| nxgx国产| 亚洲第9页| 免费大秀视频在线播放| 2021国产精品露脸在线| 美女在尿口隐私视频| 国内精品一区视频在线播放| 亚洲天堂v| 亚欧洲乱码专区视频| 国产一区二区视频在线播放| 182免费在线观看| 日韩精选视频| heyzo1754北岛玲在线视频| 丰满大屁股美女一级毛片| 天堂网www在线观看| 91精品国产综合久久精品| 2019aw网站| 免费观看无遮挡www的小视频| 国产免费福利片| 波多野结衣在线观看中文字幕| 三级黄色片在线免费观看| 免费操比视频| 国产v视频|